Description
Product name :P10-CPU Pilz Central control module
Product details:
For your safety
The unit meets all the necessary conditions for safe operation. However, please note the
following:
} Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120
VDC) are present on the unit, connected control elements and sensors must have a rated
insulation voltage of at least 250 V.
Unit features
} Positive-guided relay outputs:
– 3 safety contacts (N/O), instantaneous
– 1 auxiliary contact (N/C), instantaneous
} 1 semiconductor output
} Connection options for:
– E-STOP pushbuttons
– Safety gate limit switches
– Start buttons
– Light grids and safety switches with detection of shorts across contacts
} A connector can be used to connect 1 PNOZsigma contact expansion module
} Operating modes can be set via rotary switch
} LED indicator for:
– Supply voltage
– Input status, channel 1
– Input status, channel 2
– Switch status of the safety contacts
– Start circuit
– Errors
} Plug-in connection terminals (either spring-loaded terminal or screw terminal)
} See order reference for unit types
Safety features
The safety relay meets the following safety requirements:
} The circuit is redundant with built-in self-monitoring.
} The safety function remains effective in the case of a component failure.
} The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.
Function description
In2+
Single-channel operation: no redundancy in the input circuit, earth faults in the start
circuit and input circuit are detected.
} Dual-channel operation without detection of shorts across contacts: Redundant input circuit, detects PNOZ s4
– earth faults in the start and input circuit,
– short circuits in the input circuit and, with a monitored start, in the start circuit too.
In2-
Dual-channel operation with detection of shorts across contacts: Redundant input circuit, detects PNOZ s4
– earth faults in the start and input circuit,
– Short circuits in the input circuit and, with a monitored start, in the start circuit too,
– Shorts across contacts in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start Unit is active once the input circuit and the start circuit are closed.
} Monitored start with falling edge: Unit is active once
– the input circuit is closed and then the start circuit is closed and opened again.
– the start circuit is closed and then opened again once the input circuit is closed.
} Monitored start with rising edge: Unit is active once the input circuit is closed and
once the start circuit is closed after the waiting period has elapsed (see technical details).
} Start with start-up test: The unit checks whether safety gates that are closed are
opened and then closed again when supply voltage is applied.
} Increase in the number of available instantaneous safety contacts by connecting contact
expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expansion module.
Advantages: Foxboro, OVATION, TRICONEX, Allen-Bradley, ABB, Motorola, Siemens Moore, Ge Fanuc, Woodward, Bently Nevada and other major import brands!
We have the same series of models in stock. If you don’t find the model you need, please contact us and we will provide you with an official quotation!
Colour:new Warranty: 12 months
Lead Time:3-day working day Country of origin: Sweden
Price: Please contact us Product weight:0.515kg
Shipping Port: Xiamen, China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
The following are other related models. If you can’t find the product you need, please contact us. Thank you
All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
- Full 12-month warranty on all components
- Dedicated after-sales support
- Same-day dispatch on 1000s of parts
- All units are fully tested
- 1. Email confirmation
You will get an email confirming that we have received your enquiry. - 2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition. - 3. Your quote
You will receive a comprehensive quote tailored to your specific needs.